park-2, 2026-10-11: the DT-008 entry reader reported one card twice 560 ms
apart; the permit flow opened two sessions on the same permit and pulsed the
barrier twice (caught by the new relay-pulse log). The 24h before showed
2 entry + 2 exit opens within 2 s of the previous one.
ReadDispatcher now treats the same value from the same reader inside the
reader's debounceMs window as ONE presentation: the first verdict is replayed
(same beep, no second decision, nothing signed twice) and the repeat lands in
device_events as unsigned telemetry. Every lane and every credential kind,
so a ticket re-scanned at exit inside its grace period no longer signs a
noSession refusal for a car that just left. The window slides with repeats;
a repeat arriving while the first read is still deciding gets that decision.
The window is a Setup field on all three reader drivers ("Same-code
debounce (ms)", default 5000, 0 = off); readers configured before the field
existed get the default.
313 lines
21 KiB
Markdown
313 lines
21 KiB
Markdown
---
|
||
type: entity
|
||
tags: [parking, hardware, readers, qr, dingtian]
|
||
sources: [dingtian-dt008, dingtian-qr-linux-tool]
|
||
updated: 2026-10-11
|
||
status: open
|
||
---
|
||
|
||
# Dingtian DT-008 (QR/RFID access reader)
|
||
|
||
The project's **QR / barcode / RFID reader** — Dingtian **DT-008**, the **same vendor as the
|
||
[[dingtian-relay|relay board]]** (which is why it integrates the same HTTP-push way). A static
|
||
optical + card scanner for **QR / barcode (simple)** and **ID/IC/NFC cards**. This is the
|
||
**[[ticket-encoding|QR ticket]]** scanner (read at the pay station / exit lane) and a path for **QR
|
||
or RFID [[subscription]]** credentials. Product page: dingtian-tech.com/en_us/qr_code_reader.html.
|
||
(See [[dingtian-dt008|spec summary]] / `raw/`.)
|
||
|
||
> **Naming correction (2026-06-28).** Through most of this project this reader was wrongly called
|
||
> **"GEE" / "GEE/Fondvision" / "GEE-QR-ER80"** — a bad early assumption. There is no GEE device; it
|
||
> is the **Dingtian DT-008**. The driver id was renamed `gee-qr-reader` → `dingtian-qr-reader`
|
||
> (migration 0015 rewrites existing rows). All *protocol/behaviour* facts below were observed on the
|
||
> real hardware and remain correct — only the device identity was wrong.
|
||
|
||
## Configuring it from Linux (2026-10-08)
|
||
|
||
The Windows exe's Search / Get parameter / Set are a small binary **UDP protocol** (reader ports
|
||
24680 unicast, 24582 broadcast), reversed in [[dingtian-qr-linux-tool]]; **`scripts/dingtian_qr.py`**
|
||
reimplements it. `get <ip>` returns every setting (output type, server/port/language, card input
|
||
format, prefixes, Wiegand pulses, buzzer, fill light…), `set <ip> --field value` writes one, and
|
||
both are unicast — so they run **on the booth over SSH**, no site visit. The output-type write was
|
||
proven on the bench unit (struct diff = the one byte). Not in the protocol: symbologies, DHCP
|
||
(the exe never sends it either). First use: park-2's readers read back as **`WG26`** — the
|
||
"beeps but never pushes" case ([[site-device-installation]] §2 trap).
|
||
|
||
**In the app (same day):** the driver now speaks this protocol itself
|
||
(`packages/devices/src/drivers/dingtian-qr-config.ts`, Node `dgram`, runs in the host-network
|
||
server container). The [[first-run-setup|wizard]] **Scan** button lists readers with their mode
|
||
and current target ([[device-discovery]]); **Test** reports *not in HTTP mode* / *serial
|
||
mismatch* / *no UDP answer*; **Save** switches the reader to HTTP and set-networks its server to
|
||
this booth's IP + port, confirmed by re-read. All verified on the bench unit (WG26→HTTP; target
|
||
8080→8081→8080; struct byte-identical after). The scan GET stays unauthenticated — the reader is
|
||
identified by serial, so no push secret is stored for it.
|
||
|
||
## What it is
|
||
|
||
- **QR/barcode + card.** Reads **QR / simple barcode** AND **ID/IC/NFC cards** (~0.2 s, 0–10 cm).
|
||
(An earlier note guessed "ER80-EM = 125 kHz EM4100 prox" — that was part of the same mis-id.)
|
||
- **Interfaces: Wiegand 26/34, TCP/IP, USB, RS485** per the product page; the box leaflet
|
||
([[dingtian-dt008-box-manual]]) also lists **RS232**. (An earlier note dismissed RS-232 as a
|
||
claim from the mis-identified GEE PDF — withdrawn 2026-09-17.) For our integration it talks **HTTP over TCP/IP**; Wiegand is the reader's *output line*
|
||
on a valid read, not the host transport.
|
||
- **Power** 9–16 V DC, 800 mA; **86×86×42 mm**; −30…70 °C. Fits the [[disk-os-hardening|appliance]].
|
||
|
||
## How it integrates — HTTP-GET push, server replies the verdict (confirmed via SDK)
|
||
|
||
The protocol is settled by the **[[qrcode-sdk|QRCode SDK v1.6.5]]** (not serial as first guessed).
|
||
The reader is configured (Windows tool `QRCode_v1_6_5.exe`) with a **server IP/port** and a "server
|
||
language" (only picks the URL path, e.g. `/qa/mcardsea.php`). **On each scan it HTTP-GETs the host:**
|
||
|
||
```
|
||
GET /qa/mcardsea.php?cardid=<QR>&mjihao=<devId>&cjihao=<devSN>&status=<2 chars>&time=<utc>
|
||
```
|
||
`cardid` = scanned data; `status` low digit = **direction (1=in / 0=out)**. The host replies JSON
|
||
`{data:[{cardid,cjihao,mjihao,status,time,output}],code:0}` where reply **`status` 1=valid (beep
|
||
2×) / 0=invalid (beep 1×)**, **`output` 0=Access/1=WG26/2=WG34**, `time` syncs the clock.
|
||
|
||
This is **host-in-the-loop and SYNCHRONOUS**: the GET *is* the access query and **our reply is the
|
||
decision** — it drives the reader's beep + output. So unlike a fire-and-forget reader, the endpoint
|
||
must decide (valid/invalid, direction from `status`) and reply, then also emit a `DeviceReadEvent`
|
||
on the `read` bus for the entry/exit/permit flows ([[parking-session]], [[subscription]]) to open the
|
||
barrier. ([[device-input-flow]] is the analogous push pattern; this one also returns a verdict.)
|
||
|
||
> **This explains the "no beep":** feedback comes from the server's JSON reply, not locally. A
|
||
> non-JSON / missing reply ⇒ no beep even though the scan worked. So "no beep" ≠ "didn't scan."
|
||
|
||
- Pushes over plain **HTTP** to our `10.0.10.x` host (on the device subnet); no serial wiring, no
|
||
Wiegand-decode hardware. Suits the host-in-the-loop model; autonomy is moot anyway
|
||
([[dingtian-relay]] has no onboard ACL).
|
||
- Default IP `192.168.1.99` (set its server IP/port to this host in the vendor tool or with
|
||
`scripts/dingtian_qr.py`).
|
||
|
||
## Resolved (2026-06-16)
|
||
|
||
- Protocol = HTTP GET poll + JSON verdict (above). The earlier "serial/Wiegand, find the baud"
|
||
open questions are **moot** — it's HTTP. Wiegand is the reader's *output line* on a valid read
|
||
(the reply `output` field), not the host transport.
|
||
|
||
## As-built (2026-06-16)
|
||
|
||
- **Endpoint** `GET/POST /qa/mcardsea.php` (`apps/server/src/routes/qr-reader.ts`, public — the
|
||
reader has no auth, sits on the device subnet). Parses `cardid/mjihao/cjihao/status/time`, runs
|
||
the scan through the **read dispatcher** (permit match → permit flow; else transient exit), and
|
||
replies the **SDK verdict**: `status` 1=valid(beep 2×)/0=invalid(beep 1×), `output` 0, `time`.
|
||
- The read flows were refactored to **return a `ReadOutcome` { accepted, direction, reason }** so the
|
||
endpoint's reply reflects the real accept/reject (the dispatcher decides AND opens the barrier via
|
||
the flows). A fire-and-forget reader ignores the outcome.
|
||
- **Reader identity:** the endpoint matches the device **serial (`cjihao`)** against each reader's
|
||
`config.serial` to find its `devices` row; the dispatcher then resolves the relay that row is
|
||
**bound** to (`config.controllerId` + `relay`) and opens it. See [[entry-exit-points]].
|
||
- Verified via inject: valid permit QR → `status:1` + open; re-scan → permit exit (still valid);
|
||
unknown QR → `status:0`; reader on a barrier-less lane → `status:0`.
|
||
|
||
## Verified on hardware (2026-06-16)
|
||
|
||
Captured a real scan (vendor-emulator logger on :3000). The reader **does scan, send, and beep** —
|
||
the earlier "no beep" was simply that no server was answering on :3000 with valid JSON. Real GET:
|
||
|
||
```
|
||
GET /qa/mcardsea.jsp?cardid=52020056&mjihao=1&cjihao=H05M2AFA&status=11&time=1781634494
|
||
from 10.0.10.7 (referer: http://www.fondvision.com — the OEM is Fondvision)
|
||
```
|
||
|
||
- **PATH carries the configured "server language" EXTENSION:** this unit is set to **JSP**, so it
|
||
GETs **`/qa/mcardsea.jsp`** — NOT `.php`. Our endpoint was registered at `.php` only → it would
|
||
have 404'd the real reader. **Fixed:** the route now registers `php/jsp/asp/aspx/cgi`.
|
||
- **`cjihao` = `H05M2AFA`** is the device **serial** — the value our endpoint matches against the
|
||
reader's `config.serial`. So assign the reader with **`config.serial = "H05M2AFA"`** and bind it
|
||
to a controller relay.
|
||
- **`mjihao` = 1** (device id). `cardid` = the scanned barcode (`52020056`). `status=11`.
|
||
- The reader **beeped on the vendor reply with `status:0`** — so it acts on the reply; `0` =
|
||
invalid/1-beep as documented. A matching permit/session will return `status:1` → 2-beep accept.
|
||
|
||
## Assignment (as-built 2026-06-16)
|
||
|
||
A dedicated **`dingtian-qr-reader`** driver ([[device-registry]], reader category) models the push reader:
|
||
its one config field is **`serial`** (the `cjihao` the device reports). The admin assigns it in the
|
||
[[first-run-setup|setup wizard]] like any device (normal UUID row id), enters the serial, and binds
|
||
it to a controller relay. The QR endpoint resolves the reader by **matching `config.serial` to the
|
||
scan's `cjihao`** — not by row id — so no DB hand-editing. Set the reader's server IP/port to this
|
||
host in the **vendor tool**; assign + enter its serial + bind it here.
|
||
|
||
- Verified via inject: assign `dingtian-qr-reader` {serial:"H05M2AFA"} bound to an access relay →
|
||
a `.jsp` scan with that serial + a matching permit QR → `status:1` (2-beep accept) + open; re-scan
|
||
→ permit exit; unknown card → `status:0`; unassigned serial → `status:0` (no relay, graceful).
|
||
- Note `tcpip-reader` is the WRONG model for this device (host-connects-out, a stub) — use
|
||
`dingtian-qr-reader`.
|
||
|
||
## Open / next
|
||
|
||
- Re-test on hardware against the real app (now `.jsp`-aware + serial-resolved): scan → expect a
|
||
`status:1` 2-beep when the QR matches a permit/open session.
|
||
- `output` is replied as `0` (Access). Confirm on hardware whether the reader needs `1`/`2` (WG26/34)
|
||
to drive its access line, vs. `0`.
|
||
|
||
## Channel tagging — output prefixes close the printed-card-clone hole (2026-07-04)
|
||
|
||
The push carries ONE opaque `cardid` whether the **optical** engine decoded a QR/barcode or the
|
||
**RF** engine read a card — the server couldn't tell. And `SubscriptionFlow.match` matched by
|
||
**value only** (the stored `rf`/`qr` kind was a label). Consequence: printing a card's UID (often
|
||
written on the card face, e.g. `86A158`) as a barcode and holding it up **cloned the RF card** —
|
||
the optical decode matched the RF credential and opened the barrier. In-threat-model and cheap.
|
||
|
||
**Fix (both sides):**
|
||
- **Reader (vendor tool, both units):** set `QRCode Output Prefix` = `Q:` and `Card Output
|
||
Prefix` = `K:` (env-overridable server-side: `READER_QR_PREFIX` / `READER_CARD_PREFIX`).
|
||
- **Server:** `routes/qr-reader.ts` strips the prefix and tags the read's confirmed channel
|
||
(`DeviceReadEvent.channel: "optical"|"rf"`; kind `qr`/`card`). Enrollment capture stores the
|
||
**bare** value. `SubscriptionFlow.match` then requires **channel agreement**: an optical read
|
||
may not claim an `rf` credential (and vice versa) — a mismatch is refused AND signs a
|
||
`sub.refused.channelMismatch` **anomaly** (a clone attempt is a fraud signal). An **unprefixed**
|
||
read keeps the legacy untagged shape and matches as before — enforcement only bites where
|
||
prefixes are deployed, so an unconfigured reader never breaks.
|
||
- Bonus: every `READ` log line now carries `ch=optical|rf`, which permanently attributes any
|
||
future phantom (see below) to its engine.
|
||
|
||
⚠️ **Two device-side settings are now part of the credential contract** (they live ON the reader,
|
||
not in our DB — re-apply after any factory reset/swap): the two **output prefixes** (must match
|
||
the server's expected `Q:`/`K:`), and **`Card Input format` (currently `6H`)** — it defines the
|
||
UID shape we enroll; changing it later silently orphans every enrolled card.
|
||
|
||
## Same-code debounce at the dispatcher (park-2, 2026-10-11)
|
||
|
||
The reader can report ONE presentation TWICE. Seen live on park-2 the evening the relay-pulse logging
|
||
went in: the entry reader (`HC009E84`) pushed card `3F3AFC` at 16:25:38.119Z and again at 16:25:38.679Z
|
||
(560 ms apart); the permit flow opened **two** sessions on the same permit and the barrier was pulsed
|
||
**twice**. The 24 h before showed 2 entry + 2 exit opens within 2 s of the previous one, so it is not a
|
||
one-off. A card held a beat too long or a QR re-decoded while the hand moves does the same, and at exit
|
||
a repeat scan of a ticket inside its grace period would sign a `noSession` refusal for a car that just
|
||
left — a red row for nobody (same alarm-fatigue problem as the phantom decodes below).
|
||
|
||
**Fix (host-side, every reader, every lane, every credential kind):** `ReadDispatcher` keeps the recent
|
||
reads keyed `deviceId:kind:value`; the same value from the same reader inside the reader's
|
||
**`debounceMs`** window is one presentation — the FIRST verdict is **replayed** (the reader beeps the
|
||
same way, no second decision, nothing signed twice) and the repeat is kept as unsigned
|
||
`device_events` telemetry (`debounced: true`, `sinceMs`, `replayedAccepted`). The window slides on
|
||
each repeat (a card that keeps re-reading stays one presentation). A repeat that arrives while the
|
||
first read is still deciding awaits that same decision. The window is a **per-reader Setup field**
|
||
(`debounceMs`, "Same-code debounce (ms)", default **5000**, `0` = off) on all three reader drivers
|
||
(`packages/devices/src/drivers/reader.ts` `debounceField`); readers configured before the field
|
||
existed get the default. Plates are not affected in practice — the ANPR bridge debounces them itself
|
||
for longer ([[lane-presence-and-anpr-entry]]). Tests: `read-dispatch-debounce.test.ts`.
|
||
|
||
## ⚠️ Phantom optical decodes from sunlight patterns (park-buzi, 2026-07-04)
|
||
|
||
With the site EMPTY (pre-opening, verified live + by snapshot), the **exit reader
|
||
(`cjihao=H05MA5B0`) pushed spontaneous scans** at random afternoon times (observed 16:38–18:14,
|
||
low-western-sun hours): `cardid` values like `997492`, `389861`, `024358`, `192793` — and once a
|
||
lone **`C`**. Server logs (`READ serial=` lines) confirm the pushes carry the reader's own serial
|
||
and resolve to its assigned row, so this is **the physical reader decoding, not a network source**.
|
||
|
||
**Diagnosis:** the scan engine ships with many 1D symbologies enabled, some with weak/no checksums.
|
||
Six-digit all-numeric strings are the signature of **Interleaved 2-of-5** (even-length, digits-only,
|
||
no checksum — any high-contrast stripe pattern of the right proportions "decodes"); a lone `C` is a
|
||
**Code39/Codabar** artifact (Codabar start/stop chars are A–D). Low sun creates exactly such
|
||
patterns at a gate: the striped barrier arm, fence/railing shadows sweeping as the sun moves, glare
|
||
bands. RFID noise would instead give repeating UID-shaped values.
|
||
|
||
**Impact: noise, not risk.** Every phantom was REFUSED fail-closed; a phantom can never match a
|
||
ticket ([[ticket-encoding]] ids are 11-digit + Luhn, so a 6-digit read has nothing to match).
|
||
|
||
**Feed filter (2026-07-04 — supersedes the earlier "do not filter" position).** Initially each
|
||
phantom signed an `exit.refused.noSession` anomaly (#52–58 in the feed) and the position was to
|
||
keep it that way. The operator overruled it, correctly: red "who is trying to exit?" rows for
|
||
NOBODY train the operator to ignore the signed feed — alarm fatigue is the adversary's friend.
|
||
`read-dispatch.ts` now drops a no-match value that **cannot possibly be a credential we issue** to
|
||
UNSIGNED telemetry (`device_events`, `unrecognizedRead:true` — still auditable). "Possibly ours"
|
||
is deliberately WIDE and everything in it still signs the normal refusal anomaly: Luhn-valid
|
||
ticket shapes (a forged ticket is a real probe), `SUB-`/`SUBSESS-` prefixes, ANY read on a
|
||
confirmed-RF channel (a physical card is a real event, never sun noise), and plates (never
|
||
shape-filtered). The filter also works pre-prefix (legacy untagged reads). Still fix at the
|
||
source too:
|
||
|
||
**Fix (vendor tool, per reader — config lives ON THE DEVICE, not in our DB):** disable every
|
||
symbology except **QR + Code128** (all our credentials); if offered, set **minimum decode length
|
||
≥ 10** and require checksums. Apply to BOTH readers. ⚠️ A factory reset or a swapped unit silently
|
||
re-enables the phantom symbologies — re-apply after any reset/replacement. Physical fallback if any
|
||
noise survives: hood/visor the window, tilt it down, avoid facing the striped arm.
|
||
|
||
## ⚠️ Two units, two card sets, no overlap — 125 kHz vs 13.56 MHz (2026-09-17, unresolved)
|
||
|
||
The product page says the DT-008 reads "ID/IC/NFC cards" and the **box leaflet**
|
||
([[dingtian-dt008-box-manual]]) claims EM-ID, M1, ISO 14443A/B and ISO 15693 in one unit. Yet on
|
||
the bench 2026-09-17, with two card sets, the two units we own read **disjoint** sets:
|
||
|
||
| Unit | Serial family | Reads | Does not read |
|
||
| --- | --- | --- | --- |
|
||
| park-buzi entry/exit (bought 2026-06) | `H05M…` (`H05M2AFA`, `H05MA5B0`) | the site's enrolled cards (**125 kHz "ID"**, EM4100-class) | 13.56 MHz cards |
|
||
| lab unit (fresh, 2026-09) | `HC002721` | **13.56 MHz "IC/NFC"** cards (e.g. UID `A238BC`) | the park-buzi card set |
|
||
|
||
**The decisive test needs no hardware:** hold each card on an NFC-capable phone. A 13.56 MHz card
|
||
is detected; a **125 kHz card is invisible to a phone**. The lab reader and the phone agreed on
|
||
exactly the same set, and the other set was invisible to both — so the park-buzi set is 125 kHz and
|
||
the park-buzi readers are the 125 kHz variant. Card bodies help too: EM4100 / TK4100 / T5577 (often
|
||
a printed 10-digit decimal) = 125 kHz; Mifare / S50 / 1K / NTAG = 13.56 MHz.
|
||
|
||
Nothing in `QRCode_v1_6_5.exe` selects the frequency (no card-type field — see the screenshot in
|
||
[[site-device-installation]] §2).
|
||
|
||
**Why the lab unit does not read them is NOT settled** — the phone test only proves the park-buzi
|
||
cards are *not* 13.56 MHz. Three explanations remain, with different fixes:
|
||
|
||
1. **The park-buzi cards are 125 kHz but not EM4100** (HID Prox / Indala / AWID / a T5577 in a
|
||
non-EM format): invisible to a phone, not decoded by an EM-only front end, but read by the older
|
||
batch. Card bodies help: EM cards usually print a 10-digit decimal; HID cards carry the HID logo.
|
||
2. **The lab unit's 125 kHz front end is dead or disabled** — the leaflet says it should be there;
|
||
a firmware setting the v1.6.5 tool does not expose is possible.
|
||
3. **The leaflet is generic and units ship per variant** — the vendor can say from the two serials.
|
||
|
||
**Decisive test (cheap):** a known **EM4100 125 kHz card/keyfob** on the lab unit, held at 1–10 cm.
|
||
Reads → its 125 kHz radio works and the park-buzi cards are a different 125 kHz format (→ 1).
|
||
Does not read → unit defect or variant (→ 2/3, vendor with the serial). A USB keyboard-wedge
|
||
EM4100 reader (~10 €) additionally says outright whether the park-buzi cards are EM4100.
|
||
|
||
**Consequences (hold regardless of which explanation wins)**
|
||
|
||
- **A site's card stock and its readers must be proven together.** A card enrolled at park-buzi
|
||
is not readable by the lab unit today, whatever the reason; a replacement reader must be tested
|
||
against the site's actual cards **before** it ships, or every enrolled card is orphaned — same
|
||
class of trap as the `Card Input format`.
|
||
- **Purchase spec must name the card technology and format** the site uses (the serial family is
|
||
only a hint: `H05M…` reads park-buzi's cards, `HC…` does not). Ask the vendor (support address in
|
||
the tool's title bar) which card types a given serial decodes.
|
||
- **Bench testing park-buzi card problems on the lab unit is meaningless** until the lab unit is
|
||
shown to read the site's card type.
|
||
- **Open:** with a 13.56 MHz unit the native UID is 4 or 7 bytes, so `Card Input format = 6H`
|
||
truncates it — check on the lab unit which bytes survive and whether two cards can collide on the
|
||
6-hex value before enrolling anything against a 13.56 MHz reader ([[open-questions]]).
|
||
|
||
Record the variant on the site record next to the serial ([[site-device-installation]] §"Record").
|
||
|
||
**A phone is not a card (2026-09-17).** Tapping a phone on the 13.56 MHz unit beeps and logs a
|
||
*different* id every time (`18CA08`, `37F108`, `D5A908` three seconds apart). Read backwards
|
||
those are `08 CA 18`, `08 F1 37`, `08 A9 D5`: a first UID byte of **`08`** is the ISO 14443
|
||
marker for a **random UID**, which every phone in card-emulation mode generates per tap so that
|
||
readers cannot track the handset. So a phone can never be enrolled as an RF credential, and a
|
||
phone tap in the logs is not a clone attempt — just noise with a fresh id each time. Same for
|
||
cards with a "random ID" feature (DESFire / Mifare Plus in random-UID mode): if a card ever
|
||
enrolls but "stops matching", check whether its id changes between taps.
|
||
|
||
Incidentally this shows what **`6H` does on a 13.56 MHz unit**: the tool prints the **first three
|
||
bytes of the 4-byte UID, byte order reversed, fourth byte dropped**. Confirm against a card with
|
||
its UID printed on the body before enrolling; the dropped byte is the collision risk in
|
||
[[open-questions]] #18.
|
||
|
||
## Bench sink — `scripts/reader-sink.py` (2026-09-17)
|
||
|
||
A stdlib-only Python HTTP server that answers the push on any `/qa/mcardsea.*` path with the SDK
|
||
verdict (`--accept` → status 1 / two beeps, default status 0 / one beep), `Connection: close`, and
|
||
prints one line per read: time, source IP, `serial`, `dev`, `dir` (from the `status` low digit),
|
||
`ch` (from the `Q:`/`K:` prefix), `cardid`, path. Point the reader's *Server address / Server Port*
|
||
at the laptop (`python3 scripts/reader-sink.py -p 3000 --accept`, port 80 needs admin rights). Use it
|
||
to see the raw `cardid` a card yields, to prove a reader pushes at all, and to time the beep against
|
||
the reply. No app, no DB, no Docker.
|
||
|
||
## ⚠️ Reply MUST set `Connection: close` (verified on hardware)
|
||
|
||
The reader sends `Connection: keep-alive` but **only acts on the verdict (beep/output) once the TCP
|
||
socket CLOSES**. Fastify's default keeps the connection alive → the reader waits out a **~10 s
|
||
keep-alive timeout before beeping**, even though the server replied in ~15 ms. Every vendor demo
|
||
replies **`Connection: close`** and shuts the socket. Fix: the endpoint sets
|
||
`reply.header("connection","close")`. Symptom if regressed: correct accept/reject but a ~10 s lag
|
||
before the beep. (The request arrives fast; the delay is entirely the reader waiting for close.)
|